NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan January 7, 2002
Wipe Sampling for Dioxin Page 3
Stuvvesant High School (Manhattan! ATC Project No. 15-19125-0246
DISCUSSION
The concentrations on indoor surfaces were 0.0022 and 0.00032 nanograms per square meter
(ng/m^) . The concentration in the mixed air plenum was 0.0078 ng/m^ . No standard has been
established for dioxin on indoor surfaces. The NYSDEC acceptable soil concentration is 0.0006
parts per million (ppm) or 0.6 ppb. The EPA residential clean-up goal is 1 ppb. The levels
found in these samples appear to be below these levels.
It is not possible to determine when the 2, 3, 7, 8 - TCDD equivalents detected in these samples
were deposited. Dioxin samples were not collected from these locations prior to November 8^.
It is our pleasure to provide these indoor environmental services to the NYC Board of Education.
If you have any questions about this report, please call (212) 353-8280, extension 212.
Sincerely,
J TCASSOCIA TES INC.
James R. Cohn, CIH, CSP
Regional Manager
Industrial Hygiene Division
Attachment
CONFIDENTIAL, CITY_21MC100_003429392
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000238235
OCR can misread numbers and units. Confirm readings against the page image before using them.