NYC 9/11 Public Portal Document
ATC Environmental, Inc.
104 East 25th Street
New York, New York 10010
ATC Associates Inc. Approved N.Y. State ELAP #10879
104 East 25th Street ACCREDITED NVLAP Lab Code # 1187
New York, NY 10010 Report Date: 10/23/01
' 1 ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM)
with Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS)
Method: AHERA Final Rule, EPA Federal Register (40 CPR, Part 763), Vol. 52, No. 210, October 30, 1987
n
Sample Identification Analysis Parameters
Projeot/Site: 40 Rector Street, 40 Rector St., NY, NY TEM Sample No.: 5741 - 62039
Floors J,J^j J^j 15,JJ.
-J Date Received: 10/23/01 Grid Openings Analyzed:__ 4
Project Sample No.: 80-2 Average Grid Opening: 106.00 um
L.J
Air Volume: 1800 liters Total Area Analyzed: 0.0450 rom2
Filter Type; MCE 25 mm diam.. Pore Size; 0.45 um Analytical Sensitivity; 22.2 s/mm2
Effective Area; 385 mm2 0.0048 s/cc
FIBROUS PARTICULATES ANALYZED
Number Observed CONCENTRATION
Total
Single Matrix Total. Struct. Filter Air
Fibers Bunf is Clusters Struct. Struct >=5um 5truct/mm2 S ruct/cc nqm/m3
Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Ambiguous 0 0 0 0 0 0 0.0 0.0000 0
Total asbestos (includes ambiguous structures I 0 0 0.0 0.0000 0
Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A
No Identification 0 0 0 0 0 0 0.0 0.0000 N/A
Totals (All Structures) 0 0 0.0 0.0000 N/A
The estimated uncertainty of this analysis is 1 standard deviation.
•1 Non-asbestos fiber i.d. (EDS/SAED): None detected
• , Amphibole Asbestos Type: None detected
The Analysis was carried out in accordance with the approved TEN method.
This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
1 Roman Peysakhov Michael A. Gorycki, Ph.D.
Director of Electron Microscopy
NYC-WTC_000237473