NYC 9/11 Public Portal Document
P'!
ATC Environmental, Inc.
104 East 25th Street
LJ New York, New York 10010
r-] ATC Associates Inc. Approved N.Y. State ELAP #10879
104 East 25th Street ACCREDITED NVLAP Lab Code # 1187
New York, NY 10010 Report Date: 10/23/01
' 5 ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM)
LJ with Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS)
Method; AHERA Final Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987
Sample Identification Analysis Parameters
Project/Site: 40 Rector Street 40 Rector St., NY, NY TEM Sample No.; 5741 - 62037
Floors 1-12, 14 15, 19
Date Received; 10/23/01 Grid Openings Analyzed;__ 4
Project Sample No.: 78-2 Average Grid Opening: 106.00 urn
Air Volume: ISOO liters Total Area Analyzed; 0.0450 mm2
Filter Type: MCE 25 mm diam., Pore Size; 0.45 um Analytical Sensitivity; 22.2 s/mm2
Effective Area; 385 mm2 0.0048 s/cc
FIBROUS PARTICULATES ANALYZED
Number Observed CONCENTRATION
Total
single Matrix Total. struct. Filter Air
Fibers Bundles Clusters Struct. Struct >=5um Struct/mm2 Struct/cc ngm/m3
Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
-J Ambiguous 0 0 0 0 0 0 0.0 0.0000 0
' 1 Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0
Non-AsbestGS 0 0 0 0 0 0 0.0 0.0000 N/A
No Identification 0 0 0 0 0 0 0.0 0.0000 N/A
Totals (All Structures) 0 0 0.0 0.0000 N/A
The estimated uncertainty of this analysis is 1 standard deviation.
' ' Non-asbestos fiber i.d. (EDS/SAED) : None detected
u Amphibole Asbestos Type: None detected
The Analysis was carried out in accordance with the approved TEM method.
This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
Roman Peysakhov Michael A. Gorycki, Ph.D.
Director of Electron Microscopy
f. 1
NYC-WTC_000237472