NYC 9/11 Public Portal Document
ATC Environmental, Inc.
104 East 25th Street
New York, New York 10010
r ) ATC Associates Inc. Approved N.Y. State ELAP #10879
104 East 25th Street ACCREDITED NVLAP Lab Code # 1187
New York, NY 10010 Report Date: 10/23/01
r’T
ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM)
With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS)
Method: AHERA Final Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No, 210, October 30, 1987
.1
Sample Identification Analysis Parameters
, Project/Site: 40 Rector Street, 40 Rector St,, NY, NY TEM Sample No.: 5741 - 62015
! Fi2orsl_12j_JtLtl2^^
Date Received:10/23/01 Grid Openings Analyzed:__ 4
A Project Sample No.;56j;5 Average Grid Opening: 106.00 um
'u
Air Volume: 1800 liters Total Area Analyzed: 0,0450 mm2
;.
Filter Type: MCE 2S mm diam., Pore Size: 0.45 um Analytical Sensitivity: 22.2 s/rrwn2
Effective Area: 3S5 mm2 0.0048 s/cc
FIBROUS PARTICULATES ANALYZED
Number Observed CONCENTRATION
Total
L_; Single Matrix Total. Struct. Filter Air
Fibers Bundles Clusters Struct, Struct >=5um Struct/mn2 Struct/cc nqm/ni3
Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Ambiguous 0 0 0 0 0 0 0.0 0.0000 0
r Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0
Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A
No Identification 0 0 0 0 0 0 0.0 0.0000 N/A
Totals (All Structures) 0 0 0.0 0.0000 N/A
The estimated uncertainty of this analysis is 1 standard deviation.
’ ' Non-asbestos fiber i.d. (EDS/SAED) : None detected
t J Amphibole Asbestos Type: None detected
The Tinalysis was carried out in accordance with the approved TEM method.
This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
f.-q
Roman Peysakhov Michael A. Gorycki, Ph.D.
Director of Electron Microscopy
LJ
NYC-WTC_000237454