NYC 9/11 Public Portal Document
ATC Environmental, Inc.
104 East 25th Street
New York, New York 10010
ATC Associates Inc. Approved N.Y. State ELAP #10879
104 East 25th Street ACCREDITED NVLAP Lab Code # 1187
New York, NY 10010 Report Date: 09/28/01
ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM)
With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS)
Method: AHERA Pinal Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987
Sample Identification Analysis Parameters
Project/Site: 40 Rector Street, NY, NY TEM Sample Mo. : 5573 - 59619
Floors 5-7
Date Received:09/28/01 Grid Openings Analyzed;__ 6
Project Sample No.; 03 Average Grid Opening: 106.00 um
Air Volume; 125~0 liters Total Area Analyzed: 0.0674 mm2
Filter Type; MCE 25 mm diam., Pore Size: 0.45 urn Analytical Sensitivity: 14.3 s/mm2
Effective Area: 385 nim2 0.0046 s/cc
LJ FIBROUS PARTICULATES ANALYZED
Number Observed CONCENTRATION
Total
Single Matrix Total. Struct. Filter Air
Fibers Bundles Clusters Struct. Struct >=5u(n Struct/mm2 5truct/cc ncjm/ml
Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Ambiguous 0 0 0 0 0 0 0.0 0.0000 0
V,J
Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0
Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A
No Identification 0 0 0 0 0 0 '0.0 0.0000 N/A
Totals [All Structures) 0 0 0.0 O.OCOO N/A
The estimated uncertainty of this analysis is 1 standard deviation.
Non-asbestos fiber i.d. (EDS/SAED): None detected
Amphibole Asbestos Type: None detected
The Analysis was carried out in accordance with the approved TEM method.
This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
i-T Roman Peysakhov Michael A. Gorycki, Ph.D.
Director of Electron Microscopy