Asbestos TEM analysis results, 40 Rector Street, Sep 2001

Machine-extracted title · confidence 95%

Laboratory report detailing transmission electron microscopy analysis of air samples from floors 15-17 at 40 Rector Street received on September 28, 2001.

NYC-WTC_000237278
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

ATC Associates Inc. Approved N.Y. State ELAP #10879 104 East 25th Street ACCREDITED NVLAP Lab Code # 1187 New York, NY 10010 Report Date: 09/28/01 fuj ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) with Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Final Ruis, EPA Federal Register (40 CPR, Part 763), Vol. 52, No. 210, October 39, 1987

f3 : Sample Identification Analysis Parameters

Project/Site: 40 Rector Street, NY, NY TEI^ Sample No. : 5574 - 59643 Floors 15-17 Date Received09/28/01 • Grid Openings Analyzed:__ 6

r- Project Sample No. Average Grid Opening: 106.00 um

Air Volums: 1280 liters Total Area Analyzed:^^^^674 rnm2

Filter Type: MCE 25 mm diam., Pore Size: 0.45 um Analytical Sensitivity: 14.8 s/mm2 Effective Area: 365 mm2 0.D04S s/cc

y ------ ------ :------ ---- .--- ------------------ ; FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total single Matrix ' Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct =5um Struct/mTn2 Struct/cc ngm/m3

Chrysotile Asbestos 0 •0 0 0 0 0 0.0 0.0000 0

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 0 0.0 0.0000 0

Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0 Non-Asbestos 0 0 - 0 0 0 0 0.0 0.0000 N/A No Ident i f i c at ion 0 0 0 0 0 0 0.0 0.0000 N/A

Totals (All Structures) 0 0 0.0 0.0000 N/A The estimated uncertainty of this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED); None detected Amphibole Asbestos Type: None detected The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method. U-)

CI Analyzed by: Report Reviewed by:

Marek Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

Ui

NYC-WTC_000237278

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000237278Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →