TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.'
NitJ-ogen Dioxide
Nitrogen dioxide was not detected anywhere inside tire building (0.0 ppm). Tire outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was not occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO2, CO and TVOCs were within applicable
standards and guidelines.
2. Al l indoor measurements of relative humidity were below the ASHRAE-recomraended range
of 30 to 60 percent for occupant comfort.
3. Seven (7) .temperature measurements were above the range of 68 to 75°F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions). These readings were collected from the 5^^ floor.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-828.0, extension
261 01-212.
Sincerely,
A TC ASSOCTA TES INC. Reviewed by:
Andreas C. Andreou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21 MC100_014660006
NYC-WTC_000237005
OCR can misread numbers and units. Confirm readings against the page image before using them.