Mr. Bernard P. Orlan January 23, 2002
Indoor Air Quality Assessment Page 3
P. S. 89 (Manhattan) ATC Project No. 15-19125-0297
Real-Time Envtroniviental Measurements
ATC collected seventy-three (73) sets of real-time environmental measurements consisting of
sixty-nine (69) from inside the school building and four (4) outdoors from the playground. All
five floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:30 A.M. and concluded after
3;20P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 58.1 °F to 75.0 °F. Nine (9)
measurements were below the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature measurements at the playground ranged from 45.6 to 50.3 °F.
Relative
The relative humidity indoors ranged from 14.7 percent to 45.8 percent. Two (2) measurements
were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All
other measurements were below the recommended range. The outdoor relative humidity' ranged
from 14.7 to 41.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 527 ppm to 1128 ppm. All COg
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) COg
concentrations ranged 465 to 500 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1200 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school
building during ATC’s assessment was not occupied. .
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0
ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 38 pg/m^. All
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM.2.5
concentration for the entire school building was approximately 20 pg/m^.The outdoor respirable
particulate concentration ranged from 19 - 61 pg/m^.