January 23, 2002
Mr. Bernard P. Orlan
Director, Environmental Health & Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment
P.S.89M
201 Warren Street
New York, New York 10282
ATC Project No. 15-19125-0297
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ)
measurements collected on January 22, 2002, at the referenced school. The New York City
Board of Education (BOE) requested these measurements as part of a program to determine if
acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity,
carbon dioxide (CO2) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates (PM2.5) were also
measured.
Mr. Jimmy Choy, Industrial Hygienist of ATC’s New York City office, conducted the
assessment. ATC’s findings and conclusions are based on a visual inspection, real-time
environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551,
manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol
Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization
detector (BID).