NYC-WTC_000236945
Report of indoor air quality measurements collected on January 24, 2002, at P.S. 89M.
11 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗Report of real-time air monitoring conducted on December 15-16, 2001, at P.S. 89M regarding environmental health.
NYC-WTC_000236917–000236922OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Grlan December 19, 2001 Real-Time Air Monitoring Page 2 P.S. 89 (Manhattan) ATC Project No. 15-19125-0297
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID). Nitrogen oxides and SO2 were measured using a RAE Systems, Inc. VRAE® multi-gas detector. HoS was measured using a BioSystems PhD Ultra® gas detector.
The assessments were performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters, and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the Board of Education as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times. TABLEI TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED* ER i AGE5O- OR OU .\TZ\TIO\ 8^ _______________ J ___ _ iw Carbon Dioxide (COj) <700 parts per million (ppm) ASHRAE 62 above background level Carbon Monoxide (CO) 9 ppm. ASHRAE 62 (adopted from USEPA NPAAQS) Respirable Particulates 65 micrograms per cubic meter of USEPA NPAAQS (PM,,) air (gg/mb 24 hour average Temperature Summer: 73-79°F at 50% RH ASHICAE 55 Winter: 68-7 vF at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic 1 ppm AIHA Compounds (TVOC) Hydrogen Sulfide (H,S) 0.01 ppm (one hour) NYSDEC SuhuT Dioxide (SO2) 0.14 ppm (24-hoLir average) USEPA NPAAQS Nitrogen Dioxide (NO, ) 0.053 ppm (annual average) USEPA NPAAQS
USEPA = United States Environmental Protection Agency * Guidelines for NO are NPAAQS = National Primary Ambient-Air Quality Standard not available.
CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21 MC100_014659892
NYC-WTC_000236918
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000236945
Report of indoor air quality measurements collected on January 24, 2002, at P.S. 89M.
11 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236977
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.979
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236967
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.979
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236953
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.977
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400531
Real-time IAQ report for PS 89M covering Dec 15-16, 2001, by ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383963
ATC reports real-time air monitoring results conducted December 15–16, 2001 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000325955
Memo presenting real-time air monitoring results for PS 89M, December 2001.
15 shared non-person entities · 1 shared topics · similarity 0.986
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000208064
ATC Associates report on real-time air monitoring conducted at P.S. 89M in December 2001 to assess environmental conditions.
14 shared non-person entities · 1 shared topics · similarity 0.984
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177887
Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.
13 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396218
ATC monitoring report detailing real-time IAQ measurements at PS 234 following BOE request, Dec 8–12, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.980
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373506
Real-time IAQ monitoring report for P.S. 234M in December 2001 and January 2002.
13 shared non-person entities · 1 shared topics · similarity 0.980
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291841
Indoor air quality measurements report for 90 Trinity Place, May 2002.
10 shared non-person entities · 1 shared topics · similarity 0.976
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000400531
Real-time IAQ report for PS 89M covering Dec 15-16, 2001, by ATC Associates.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000208064
ATC Associates report on real-time air monitoring conducted at P.S. 89M in December 2001 to assess environmental conditions.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177887
Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.
Similarity score 0.979 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396218
ATC monitoring report detailing real-time IAQ measurements at PS 234 following BOE request, Dec 8–12, 2001.
Similarity score 0.978 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260325
ATC report of IAQ measurements taken May 10, 2002 at the referenced school.
Similarity score 0.974 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
Similarity score 0.974 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000400531
Real-time IAQ report for PS 89M covering Dec 15-16, 2001, by ATC Associates.
Similar indexed content
NYC-WTC_000383963
ATC reports real-time air monitoring results conducted December 15–16, 2001 at the referenced school.
Similar indexed content
NYC-WTC_000325955
Memo presenting real-time air monitoring results for PS 89M, December 2001.
Similar indexed content
NYC-WTC_000208064
ATC Associates report on real-time air monitoring conducted at P.S. 89M in December 2001 to assess environmental conditions.
Similar indexed content
NYC-WTC_000177887
Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.
Similar indexed content