AMBIENT AIR AND DUST SAMPLING PROTOCOL for PS/IS89M. Page 6 of 8
SILICA
• First floor hallway outside cafeteria - 2 samples.
• Cafeteria - one sample.
• Gymnasium - one sample.
• Auditorium - one sample.
• Classroom with north side unit ventilators - one sample immediately after the last class.
Classroom with east side unit ventilators - one sample immediately after the last class.
• Classroom with south side unit ventilators - one sample immediately after the last class.
• Second floor Hallways south end - one samples immediately after the last class.
Fourth floor Hallways south end - one samples immediately after the last class.
All sample collected shall be analyzed utilizing the NIOSH 7500 method for respirable silica.
Since, there are no regulatory standards for Mineral Dust in non-industrial buildings, such as
offices and schools at this time, the OSHA standard 1910.1000 TABLE Z-3 shall be utilized
(per the request of PA consultant).
Results from samples collected shall be reported to BOE, UFT, School Principal and the PA
consultant within 72 hours from the collection day.
In the event that unsatisfactory results are obtained, the following actions are to be
implemented:
1. Perform general dust clean up of all areas/classrooms with unsatisfactory results.
2. Re-test said areas following clean up.
3. Floor mats and/or other dust control devises shall be placed at points of entry.
Actions 1,2 shall be repeated until satisfactory results are obtained.
DIOXIN WIPE SAMPLES
• First floor hallway, near north entrance - one sample.
• First floor hallway, near south entrance - one sample.
• Second floor hallway, near staircase - one sample.
All sample collected shall be analyzed utilizing the EPA 8290 PCDD/DF Dioxin Furan
method.
Results from samples collected shall be reported to BOE, UFT, School Principal and the PA
consultant in 15 business days from the day of sampling.