AMBIENT AIR AND DUST SAMPLING PROTOCOL for PS/IS89M. Page 3 of 8

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

’A Ik lUI CT nil r" to I t rV T _____________ ■HI ______ iB OB Temperature (T) Summer; 73-79°F at 50% RH ASHRAE55 Winter: 68-75°F at 50% RH Relative Humidity (RH) 30 - 60 % ASHRAE 55 Carbon Dioxide (CO2) <700 parts per million (ppm) ASHRAE 62 above background level Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in (CO) ________ ASHRAE 62) Total Volatile Organic 1 ppm AIHA Compounds (TVOC) Respirable Particulates 65 micrograms per cubic USEPA NPAAQS (PM2.5) meter of air (ug/m") USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association ASHRAE = American Society of Heating, Refrigerating, and Air-Conditioning Engineers

Results from samples collected each day shall be reported verbally, no later than Sam the next day, to BOE, UFT, School Principal and the PA consultant. A written report shall be delivered or faxed by the end of the day.

In the event that real-time measurements of Temperature, Relative Humidity, and/or CO2 exceed the cited Target Guidelines, the following actions are to be taken:

1. Building engineering controls shall be adjusted and/or implemented to improve conditions. In the event, that real-time measurements of respirable particulates exceed the cited Target Guidelines, BOE will immediately notify the UFT, the school principal, the school custodian and the PA consultant. The said parties will assess the situation and implement the appropriate response action(s).

In the event, that CO inside the school measured above the cited Target Guidelines (9ppm), BOE will immediately notify the UFT, the school principal, the school custodian and the PA consultant. The said parties will assess the situation and implement the appropriate response action(s).

NYC-WTC_000236906

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000236906Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →