AMBIENT AIR AND DUST SAMPLING PROTOCOL for PS/IS89M. Page 3 of 3
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Temperature (T) Summer; 73-79° F at 50% RH ASHRAE 55 Winter; 68-75T at 50% RH Relative Humidity (RH) 30 - 60 % ASHRAE 55 Carbon Dioxide (CO2) <700 parts per million (ppm) ASHRAE 62 above background level Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in (CO) ASHRAE 62) Total Volatile Organic 1 ppm AIHA , Compounds (TVOC) Respirable Particulates 65 micrograms per cubic USEPA NPAAQS -G (PM2.5) meter of air (ug/m^) - For General Population._______ 40 micrograms per cubic USEPA meter of air (gg/m^) - Recommended for Sensitive individuals and Children.
USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association ASHRAE = American Society of Heating, Refrigerating, and Air-Conditioning Engineers
Results from samples collected each day shall be reported verbally, no later than Sam the next day, to BOE, UFT, School Principal and the PA consultant. A written report shall be delivered or faxed by the end of the day.
In the event that real-time measurements of Temperature, Relative Humidity, and/or CO2 exceed the cited Target Guidelines, ATC shall immediately notify BOE representative Mr. Mohamed Hemida, the UFT and the PA consultant. BOE shall notify the school principal, the school custodian and the plant manager. The said parties will assess the situation and implement the appropriate response action(s) immediately.
The following actions are to be taken;
1. Building engineering controls shall be adjusted and/or implemented to improve conditions.
CITY_21MC100_009214632
NYC-WTC_000385799
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000385819
Lab protocol outlining ambient air and dust sampling for asbestos at IS 89 Manhattan.
16 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385830
protocol for ambient air and dust sampling inside PS 89 Manhattan following WTC cleanup.
16 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385808
Protocol detailing daily ambient air sampling inside the IS 89 building.
16 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000200230
Draft protocol document establishing daily ambient air and dust sampling procedures for asbestos monitoring at P.S./I.S. 89 Manhattan.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324167
Ambient air sampling protocol for PS 89 Manhattan; asbestos IAQ plan.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324211
Ambient air sampling protocol for PS 89 Manhattan; asbestos IAQ.
16 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324176
Ambient air and dust sampling protocol for PS 89 Manhattan, asbestos monitoring.
16 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324159
Ambient air/dust protocol for PS 234 Manhattan; asbestos IAQ.
16 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000234651
Draft protocol document outlining daily asbestos testing procedures for ambient air at P.S./I.S. 89 Manhattan following the WTC tragedy.
16 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236847
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000453730
Draft ambient air and dust sampling protocol for IAQ/asbestos monitoring at PS 89 Manhattan.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236904
Draft protocol for daily ambient air and dust sampling at P.S./I.S. 89 to monitor potential asbestos contamination.
16 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000324167
Ambient air sampling protocol for PS 89 Manhattan; asbestos IAQ plan.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000200230
Draft protocol document establishing daily ambient air and dust sampling procedures for asbestos monitoring at P.S./I.S. 89 Manhattan.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385819
Lab protocol outlining ambient air and dust sampling for asbestos at IS 89 Manhattan.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385830
protocol for ambient air and dust sampling inside PS 89 Manhattan following WTC cleanup.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385808
Protocol detailing daily ambient air sampling inside the IS 89 building.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324211
Ambient air sampling protocol for PS 89 Manhattan; asbestos IAQ.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000200230
Draft protocol document establishing daily ambient air and dust sampling procedures for asbestos monitoring at P.S./I.S. 89 Manhattan.
Similar indexed content
NYC-WTC_000324167
Ambient air sampling protocol for PS 89 Manhattan; asbestos IAQ plan.
Similar indexed content
NYC-WTC_000385819
Lab protocol outlining ambient air and dust sampling for asbestos at IS 89 Manhattan.
Similar indexed content
NYC-WTC_000324211
Ambient air sampling protocol for PS 89 Manhattan; asbestos IAQ.
Similar indexed content
NYC-WTC_000324176
Ambient air and dust sampling protocol for PS 89 Manhattan, asbestos monitoring.
Similar indexed content