NYC 9/11 Public Portal Document SciL^ob#: 202031636 Fa 1 Of 1

Client Name: TRC Environmental Corporation Phase Contrast Microscopy (PCM) Fiber Results 35052-0000-00007; New York Law Department; 100 Church Street; AMBIENT Flow Air Fiber Fibers SciLab Client Rate Duration Filtered Density Cone. Fields Fibers TWA Sample # Sample # / Location Collected (liters/min.) (min.) (liters) (Fibers/mm^ ) (Fibers/cc)

01 GS-3/6/02-ASB-0325 3/6/02 5 300 1500 100 42 53.50 0.014 3rd Floor Hallway Near 3-171 02 GS-3/6/02-ASB-0326 3/6/02 5 240 1200 100 29 36.94 0.012 3rd Floor Hallway Near WS 3-305 03 GS-3/6/02-ASB-0327 3/6/02 5 300 1500 100 4 5.10 < 0.002 WS 3-322 D 04 GS-3/6/02-ASB-0328 3/6/02 5 300 1500 100 3 3.82 < 0.002 Rm 3-223 05 GS-3/6/02-ASB-0329 3/6/02 0 0 0 100 0.5 0.64 Blank Footnotes: J 06 GS-3/6/02-ASB-0330 3/6/02 0 0 0 100 0.5 0.64 Blank Footnotes: I Reporting Notes: „ (1) Fibers/cc cannot beTt^enf^^for satopes (or blilanks) with no air volume. Analyzed by: Marvin RrntherX ft vO~l>T>N\ ____ ; Date Analyzed: 3/7/02 Samples analyzed by NIOSH 7400(A) Method, Issue tt2, 8/15/94: Limit of Detection= 5.5 fibers per 100 fields or 7 fibers/tnm2: This report relates ONLY to the sample analysis expressed as fibers/sq mm of filter area: ND=No fibers observed: NA= Not Analyzed; Walton-Beckett graticle field area = 0.00785 mm2; TWA = 8 Hr TWA calculation assumes zero exposure for remainder of 8 hr period not sampled: Upper 95% Confidence limit (Employers Compliance Test)- Calculated as a one sided UCL to determine 95% certainty of compliance with the 0.01 fiber/cc standard: Estimated relative standard deviation: Intralab Sr=O.4O5, Interlab Sr=0.45, New York samples (NYSDOH ELAP Lab # 11480): National Institute of Standards and Technology Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the laboratory. AIHA # 102843.

NYC-WTC_000235522

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000235522Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →