Sc b#: 202022696 P 1 of 1 .
Client Name; TRC Environmental Corporation
Phase Contrast Microscopy (PCM) Fiber Results
35052-0000-00007; New York City Law Dept.; 100 Church St./ OSHA
Flow Air Fiber Fibers
SciLab Client Rate Duration Filtered Density Cone.
Fields Fibers TWA
Sample # Sample # / Location Collected (liters/min.) (min.) (liters) (Fibers/mm^ ) (Fibers/cc)
01 GS-21602-OSHA-0620 2/16/02 2 540 1080 100 2 2.55 < 0.002
Joshua Figueroa
02 GS-21602-OSHA-0621 2/16/02 2 540 1080 100 0.1 0.13 < 0.002
Ceasar Rodriguez
03 GS-21602-OSHA-0622 2/16/02 0 0 0 100 0.5 0.64
Field Blank Footnotes: /
04 GS-21602-OSHA-0623 2/16/02 0 0 0 100 0.5 0.64
Field Blank Footnotes: 1
Reporting Notes:
(1) Fibers/cc cannot be^cs(ij^d for feaiMles (or blanks) with no air volume.
Analyzed by: Marvin ; Date Analyzed: 2/18/02
Samples analyzed by NIOSH 7400(A) Method, Issue #2, 8/15/94: Limit of Detections 5.5 fibers per 100 fields or 7 fibers/mm2: This report relates ONLY to die sample analysi s expressed as fibers/sq mm of filter area: ND=:No fibers observed: NA= Not
Analyzed; Walton-Beckett graticle field area = 0.00785 mm2; TWA = 8 Hr TWA calculation assumes zero exposure for remainder of 8 hr period noE sampled: Upper 95% Confidence limit (Employers Compliance Test)- Calculated as a one sided UCL to
determine 95% certainty of compliance with the 0.01 fiber/cc standard: Estimated relative standard deviation: Intralab Sr=0.405, Interlab Sr=0,45, New York samples (NYSDOH ELAP Lab # 11480): National Institute of Standards and Technology
Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the laboratory. AIHA # 102843.