B9-24-i6C.24. 2CQ1XI 5:32PMe associates llc 10 = 84.5 94a' S4.86h.1 399 • p. 5P88/19

Adelaide Associates, LLC 3

Interpretation of results;

Measurements of Carbon Dioxide were taken at all interior room sample locations. Carbon dioxide measurements indicate whether there is sufficient air exchange within an occupied space. By comparing the outdoor spot readings to the Interior readings, you can estimate a "lag time".

Also, ASHRAE, NiOSH and GSA FPMR standards are NOT law. Only the OSHA PEL is a "legal’' requirement However the "spirit' of an indoor air quality ©valuation is to evaluate the indoor environment from both a comfort and health perspective and provide recommendations which will improve the environment

Both ASHRAE Standard 62-1999 (The American Society of Heating, Refrigeration, and Air Conditioning Engineers) and the GSA FPMR (Federal Property Management Requirements) recommend levels below 1000 ppm for comfort and general purging of natural and artificial irritants.

We found the levels of carbon dioxide to be below 1000 ppm at all locations, showing sufficient air exchange.

Carbon Monoxide readings were taken using a Kane-May direct reading instrument, electronically zeroed, and sensitive to 1 ppm of CO, Levels measured throughout the facility were at non-detected (less than 1 ppm). This indicates vehicular traffic exhaust is not directed into the air distribution system, and since there were no other sources of combustion or heating, carbon monoxide is not a concern in this suite.

Industrial Hygl^nt /nvutiffattons /OSHA CompJlanct Swietg /'Asbestos iLead Oanautffng Community NoisaAssSiSmsni/Hsisrdcus Maioris! Absttmtnt

Race!3 Tiini San.24. 4:21PM

CITY_21MC100_011835484

NYC-WTC_000232955

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000232955Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000104673 · Box DEP Box 36

Report from Consulting & Testing Services, Inc. regarding air quality monitoring at NYU Downtown Hospital in September 2001.

Similar indexed content

Compare copies and versions →