Measurements of Carbon Dioxide were taken at all interior room sample
locations. Carbon dioxide measurements indicate whether there is
sufficient air exchange within an occupied space. By comparing the
outdoor spot readings to the Interior readings, you can estimate a "lag
time".
Also, ASHRAE, NiOSH and GSA FPMR standards are NOT law. Only the
OSHA PEL is a "legal’' requirement However the "spirit' of an indoor air
quality ©valuation is to evaluate the indoor environment from both a
comfort and health perspective and provide recommendations which will
improve the environment
Both ASHRAE Standard 62-1999 (The American Society of Heating,
Refrigeration, and Air Conditioning Engineers) and the GSA FPMR
(Federal Property Management Requirements) recommend levels below
1000 ppm for comfort and general purging of natural and artificial irritants.
We found the levels of carbon dioxide to be below 1000 ppm at all
locations, showing sufficient air exchange.
Carbon Monoxide readings were taken using a Kane-May direct reading
instrument, electronically zeroed, and sensitive to 1 ppm of CO, Levels
measured throughout the facility were at non-detected (less than 1 ppm).
This indicates vehicular traffic exhaust is not directed into the air
distribution system, and since there were no other sources of combustion
or heating, carbon monoxide is not a concern in this suite.