Mr. Bernard P. Orlan February 4. 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0297
* The measurements made during this assessment were instantaneous readings, the NP.Y\QS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• Tire interior of the building appeared clean and free of dust and debris:
• The building was occupied by staff at the time of the assessment;
• T here was a lot of activity (e.g. moving) in the building;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO and TVOCs were within applicable standards and guidelines:
2. All measurements of PM2,5 were below the NPAAQS of 65 ug/m^; Thirteen (13)
measurements were above the EPA recommended level of 40 ug/m^;
3, All indoor measurements of relative humidity were within the ASHRAE-recommended
range of30 to 60 percent for occupant comfort;
4. All but two (2) temperature measurements were below the range of 68 to 75° F (at 50
percent relative humidity) recommended by ASHRAE Standard 55 -1992 during the heating
season (wintertime conditions).
It IS our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-S2SO, extension
261 or 212.
Sincerely,
ATC ASSOCIATES
James R. Cohn, CIH, CSP
Regional Manager
Industrial Hygiene Division