Mr. Bernard P. Orlan February 4, 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Proiect No. 15-19125-0297
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOCConcentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied by staff at the time of the assessment;
• There was a lot of activity (e.g. moving) in the building;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO and TVOCs were within applicable standards and guidelines;
2. All measurements of PM2.5 were below the NPAAQS of 65 ug/m^; Thirteen (13)
measurements were above the EPA recommended level of 40 ug/m^;
3. All indoor measurements of relative humidity were within the ASHRAE-recommended
range of30 to 60 percent for occupant comfort;
4. All but two (2) temperature measurements were below the range of 68 to 75® F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating
season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. . If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
ATC ASSOCIATES
James R. Cohn, CIH, CSP
Regional Manager
Industrial Hygiene Division
Attachment