NYC 9/11 Public Portal Document I□:2125534062 PAGE 3/15 MftY-30-02 16:20 FROM:MOODYS INVESTORS SVR

lottsductisiu At the request of Mr. Tom HincWy. S & B representatives conducted a survey of the building located at 176 Broadway, In New York, New York. This survey was conducted to determine if any of a variety of contaminants known to have been released from the World Trade Center disaster were present in HVAC systems of the building.

SitUTThTT

On 29 April 2002, Mr. Rohde of S & B Environmental conducted a survey of apartments 4- D, PH-B 10-A, 3-D, and 10-E. During the survey, samples were collected from one supply point in each apartment. At each sample point, asbestos, lead, mercury, pulverized glass, and molds, and fungus were evaluated. This survey was a preliminary, limited evaluation.

The samples for lead, yielded results ranging from 160 to 1085 micrograms per square foot. These are moderately high readings for lead.

The asbestos samples yielded results ranging horn <3,165 to over 308,662 structures per centimeter squared on ths inside duct surfaces. These reading are indications of moderate to severe contamination inside the duct system.

The mercury samples yielded results ranging from 2.25 to 28.5 micrograms per foot square foot on the inside duct surfaces. These reading are indications of moderate to severe contamination inside the duct system.

The pulverized glass samples yielded results ranging from 1 to 16 % in the dust inside the ducts. These reading are indications of moderate to severe contamination inside the duct system.

The mold and fungus readings found several common materials, as well as several that could not be identified do to deformity, or decay. These results are typical, and do not alone present a condition of concern.

The following table presents the findings by apartment, and sample type.

Table 1 > Results of sampling Apartment Asbestos (str/cm^) Lead (ugm®) Mercury ug/ff Pulverized Glass (%) Molds & Fungus 4-D <3,165.76 1085 28.5 16 Present PH-B 4,748.84 214.2 14.7 8 Present 10-A 63,315.20 553.0 5.90 4 Present 3-D 5,144.38 160.2 2.25 1 Present 10-E 306,662.00 691.4 3.42 2 Present Overall, the sample results indicate serious contamination of the HVAC duct work. This survey was very limited in scope, and without further sampling. It should be assumed that similar levels of contamination will be present in other HVAC systems through out the building.

CITY_21MC100_000914562 NYC-WTC_000208413

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000208413Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →