Mr Bernard P Orlan March 22 2002 Indoor Air Quality Assessment Page 4 H S for Leadership & Public Service (M894) ATC Project No 15 19125 0290 recommended concentration for sensitive individuals such as asthmatic people and children of 40

* The measurements made during this assessment were instantaneous readings the NPAAQS is a 24 hour average

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building These concentrations were below the AIHA guideline for odor control of 1 ppm The outdoor TVOC concentration was also 0 ppm

OBSERVATIONS

During this assessment ATC noted the following • The interior of the building appeared clean and free of dust and debris • The building was occupied at the time of the assessment • No smoke odor was detected in the building

FINDINGS

Based on the real time measurements the following fmdmgs are presented

1 Concentrations of CO and TVOCs were below applicable standards and guidelines 2 Ninety six (96) indoor measurement for temperature were above and thirty one (31) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heatmg season (wintertime conditions) 3 Ninety nine (99) of the indoor measurements for relative humidity were below and twenty nine (29) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort 4 One of the indoor measurements for CO2 was above the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The highest reading (1233 ppm) was measured in room 815 at 2 42 PM with 38 occupants Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The pnmary source of CO2 indoors is occupant respiration 5 All of the indoor measurements for PM2 5 were below the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter One (1) of the one hundred thirty seven (137) instantaneous indoor readings was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children All of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^

CITY_21MC100_003085552

NYC-WTC_000189319

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000189319Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180183

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.

Similar indexed content

Compare copies and versions →