MUNICIPAL TESTING LABORATORY, INC.
102 NEW SOUTH ROAD, HICKSVILLE, NEW YORK 11801, 516-938-7120, 516 938-5107 FAX
CONCRETE REPORT
ent: LIRO Group/NYC DDC Attn: Mike Bailey Report Date: 8/26/02
tress: Six Aerial Way Report Number: DI 333 Lab#: 1798
Syosset, NY 11791 Date Cast: 6/7/02
Project: HWM WTC A2/A3
Contractor: Tully/Grace JV Concrete Plant: Ferrara Bros.
Strength PSI: 3200 Yards Placed:
FIELD INSPECTION REPORT
Pour Location for Set # 1: Church St. @ Franklin
Pour Location for Set # 2:
Pour Location for Set # 3:
Tests made in accordance with ASTM: Yes Not Known X Field Inspector (s) : Client
ASTM C 39 COMPRESSIVE STRENGTH TESTS
—, =
AREA: 28.27 Cylinder Dia: 6"
Cylinder Date Date Slump Air Unit Wt. Temp F. Truck Tested Load strength Required Type
ID # Cast Tested C143 ;173, C23 C138 C1064 No. Age KN PSI Strength Frac
Cylinder Set # 1
T5701 6/7/02 6/14/02 2.5 5.5 68 7 345.8 2,750 3,200 A
T5702 6/7/02 7/5/02 2.5 5.5 68 28 506.4 4,030 3,200 A
T5703 6/7/02 7/5/02 2.5 5.5 68 28 510.6 4,060 3,200 A
T^h^der Set # 2
Cylinder Set # 3
Remarks: Cylinders Made By Client
Reviewed By:_
Laboratory Director
Richard Kasparian, P.E
Tests are conducted in accordance with ASTM C-39 or AASHTO T-22, By technicians certified by ACI. Municipal Testing is inspected by the Cement and Concrete Reference Laboratory of The National Institute of