Mr. Bernard P. Orlan March 6. 2002
Indoor Air Quality Assessment Page 4
If S. I5QM_________________ ATC Protect No. 15-19125-0289
The measurements made during this assessment were instantaneous readings, the NTAAQS is
a 24-hour average.
Tl^'OC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor T\'OC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following;
• There was construction work going on in the plaza;
• JTc school building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
leased on the real-time measurements, the following findings are presented:
1. Concentrations of CO, CO2 and TVOCs were within applicable standards and guidelines;
None of the PM2.5 measurements were above the NP.AAQS of 65 pg/m^ or above the
USEP..A recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and
children.
3. Twenty -eight (28) of the temperature measurement were above the range of 68 to 75^ F (at
50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the
heating season (wintertime conditions).
4. All indoor measurements of relative humidity were below the ASHRAE recommended range
of 30 to 60 percent for occupant comfort.
it IS our pleasure to provide these indoor air quality sertdces to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely, Reviewed by:
.4 TC ASSOCIA TES LNC.
' ’i'lannis Efstathiou James R. Cohn, CIH, CS?
Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_002954336