Mr. Bernard P. Orlan March 26, 2002
Indoor Air Quality Assessment Page 4
_________________ ATC Project No. 15-I9125-(1289
The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
ri''OC Concentrations
TVOCs were not detected an>where inside the building (0.0 ppm). Tlie outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, AT(/ noted the following;
• There was construction work going on in the plaza;
• The school building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
I. Concentrations of CO, COp and TVOCs were within applicable standards and guidelines;
2 . None of'the indoor or outdoor PM2 5 measurements were above the NP.VAQS of 65 pg/m^
or above the US.EPA recommended PM2.5 concenhation of 40 pg/m^ for sensitive
individuals and children.
3. All of the temperature measurements were within the range of 68 to 750 f Qt 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions).
4. All measurements of relative humidity were below the ASHRAE recommended range of 30
to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280. extension
211 or 212.
Sincerely, Review^ed by:
.4 TC ASSOCIA TES INC.
y ’ihannis Efstamiou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment