Mr. Bernard P. Orlan March 14, 2002
Indoo- Air Quality Assessment Page 4
P. S. 150M ATC Project No. 15-19125-0289
* The measurements made during this assessment were instantaneous readings, the NPA.A.QS is
a 24-hour average.
Tl'OC Concentj^ions
TVOCs W'ere not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• There was not construction work going on in the plaza;
• The school building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
I. Concentrations of CO, CO2 and TVOCs were within applicable standards and guidelines;
2. None of the indoor PM;?.5 measurements were above the NPAAQS of 65 pg/m- or above
the USEPA recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and
children. All of the outdoor PM2.5 measurements were below' the NPAAQS of 65 pg^m-
but above the USEPA recommended PM2 5 concentration of 40 pg/m^ for sensitive
individuals and children.
3. Eighteen (18) of the temperature measurements were above the range of 68 to 75o F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating
season (wintertime conditions).
4. All measurements of relative humidity w ere w'ithin the ASHRAE recommended range of 30
10 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, e.xtension
211 or 212.
Sincerely, Reviewed by:
A TC ASSOCIA TES INC.
?
f ■
Yiannis Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hy giene Division