Mr. Bernard P. Orlan October 29. 2001 indoor Air Quality Assessment Page 4 Siuvvesant High School (M477) ATC Project No. 15-19125-0246

TI'OC Cvncenlration

TVOC concentrations indoors were 0.0 ppm for all readings. These concentrations were below the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the.following: • The interior of the bui lding appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • All windows were closed except for windows in Room 1004; • Relative humidity in room 901 was 72.8%. The univent in this room may not be working; • No smoke odor was detected in the building;

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards. and guidelines.

2. Five COg measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. One (1) temperature measurement was below the range recommended by ASHRAE 62-1999.

4. Two (2) relative humidity measurements were within the range recommended by ASHRAE 55-1992. All other measurements were below the recommended range except the one collected from room 901 which it was above.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO? levels indicate the need for increased outdoor air.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following:

• Keep comfort parameters within established guidelines by using adequate ventilation, • Discontinue daily TVOC measurements; TVOCs have not been detected since daily measurements began October 9, 2001; • Ensure that the HVAC system is operating properly: • Consider upgrading the fillers on the HVAC intakes;

CITY_21MC100_003100283

NYC-WTC_000182672

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000182672Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →