NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 11,2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance tMSBSi ATC Project No. 15-19125-0291
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. All eighty-eight (88) measurements were within the ASHRAE-recommended range of 30 to
60 percent for occupant comfort. Eighty-eight (88) measurements were within the ASHRAE
recommended range.
3. Twenty eight (28) of the indoor measurements were below and sixty (60) were within the
range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard
55-1992 during the heating season (wintertime conditions).
4. One (1) of the indoor measurement for carbon dioxide was above the ASHRAE Standard 62-
1999 recommended maximum concentration of <700 ppm above the background level. The
highest reading was measured in hallway outside Gym approximately at 10:10 AM.
5. None of the indoor measurements were above the NPAAQS of 65 pg/m^. Four (4) of the
eighty-eight (88) indoor instantaneous PM25 concentration were above USEPA
recommended concentration of 40 pg/m^ for sensitive individuals / children. All of the
outdoor measurements were above the NPAAQS of 65 pg/m^ and the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals / children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
356 or 212.
Sincerely,
A TC ASSOCIA TES INC.
Review
Prasad Doddapaneni James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CONFIDENTIAL, CITY_21MC100_003461970
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000179975
OCR can misread numbers and units. Confirm readings against the page image before using them.