Indoor Air Quality Report, March 8, 2002, NYC School

Machine-extracted title · confidence 98%

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.

NYC-WTC_000179972–000179975
Page image
Scanned page image, NYC-WTC_000179975
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 11,2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance tMSBSi ATC Project No. 15-19125-0291

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. All eighty-eight (88) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Eighty-eight (88) measurements were within the ASHRAE recommended range. 3. Twenty eight (28) of the indoor measurements were below and sixty (60) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. One (1) of the indoor measurement for carbon dioxide was above the ASHRAE Standard 62- 1999 recommended maximum concentration of <700 ppm above the background level. The highest reading was measured in hallway outside Gym approximately at 10:10 AM. 5. None of the indoor measurements were above the NPAAQS of 65 pg/m^. Four (4) of the eighty-eight (88) indoor instantaneous PM25 concentration were above USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. All of the outdoor measurements were above the NPAAQS of 65 pg/m^ and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 356 or 212.

Sincerely, A TC ASSOCIA TES INC. Review

Prasad Doddapaneni James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003461970 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000179975

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000179975Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180188

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in April 2002.

Similar indexed content

NYC-WTC_000180183

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.

Similar indexed content

NYC-WTC_000179990

Letter from ATC Associates reporting indoor air quality measurements collected at a school on April 9, 2002.

Similar indexed content

Compare copies and versions →