IAQ Report Cover Letter, 90 Trinity Place, May 2002

Machine-extracted title · confidence 95%

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.

NYC-WTC_000180220–000180223
Page image
Scanned page image, NYC-WTC_000180223
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 22, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894j ATC ProjeerNo. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AHIA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Thirteen (13) of the indoor measurements for temperature was below and one (1) was above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. Seventy-nine (79) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Twenty-two (22) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. 5. None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or 212.

Sincerely, .1TC ASSOCIA TES INC. Reviewed by

Yiannis Efstathiou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003464373 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000180223

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000180223Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →