Tci)i/}crctiLii-L'
Indoor dry bulb temperature measurements ranged from 68.7 °F to 75.5 °F. Only one (I) measurement was above the range .of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). This measurement was collected from room 23 I. The outdoor temperature range was 36.9 to 38.5 °F.
Relciiive Humidiiv
The relative humidity indoors ranged from 22.1 percent to 33.7 percent.. Only sixteen (16) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the ASHRAE-recommended range. The outdoor relative humidity range was 26.9 and 32.1 percent.
Carbon Dioxide Concentrcil.ion
Carbon dioxide concentrations indoors ranged from 569 ppm to 1824 ppm. Eighteen (18) COo measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COn concentrations were 445 ppm and 468 ppm. Therefore, the maximum acceptable level of COn at this location was 1168 ppm (background level + 700 ppm). The highest reading, 1824 ppm, was in Room 738. Rooms with COo levels above the recommended maximum were found on 3'*^, 4fl\ 5*^1'’, 7^''’, 9^1'' and 10**'* floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COn indoors is occupant respiration.
Carbon Monoxide Concenlixjtion
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9, ppm. The outdoor CO concentration was 2 ppm.
Rexpiruble Parliciilal.es fPMi, .
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 30 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in' aerodynamic diameter. The outdoor respirable particulate concentrations were 15 and 32 pg/m^.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''^. 6^1'* and 7^*'' floors (See Attachment 1). The PM2.5 concentration range for those rooms- was 11-23 pg/mJ with an average of approximately 18 pg/m^. The PMa j concentration range for the other.rooms was 8 - 30 pg/m-’ with an average of approximately 14 pg/m-’. The average PMt 5 concentration for the entire school building was approximately 15 pg/m-’. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were, placed in Rooms 327. 333. 638 and 740. The PMo j concentration range for these rooms was 9 - 35 pg/m-’ with an average of approximately 22 pg/m^.
CONFIDENTIAL, CITY_21MC100_003457522 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000179061
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
10 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177858
Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 29, 2002, to evaluate building contamination.
10 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗9 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗9 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.976 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.970 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.970 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.969 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182868
Report detailing indoor air quality measurements collected at PS 234M on February 1, 2002, to evaluate conditions prior to re-occupancy.
Similarity score 0.969 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
NYC-WTC_000177858
Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 29, 2002, to evaluate building contamination.
Similar indexed content