April 17, 2002
Mr. Bernard P. Orlan
Director, Environmental Health & Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101 -4008
Re: Indoor Air Quality Assessment
P.S. 150M
334 Greenwich Street
New York, New York 10013
ATC Project No. 15-19125-0289
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ)
measurements collected on April 16, 2002, at the referenced school. The New York City Board
of Education (BOE) requested these measurements to evaluate air quality in the school building
prior to re-occupancy.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity,
carbon dioxide (CO,) and carbon monoxide (CO).
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551,
manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol
Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of Total Volatile Organic Compounds (TVOCs) using a RAE
Systems, Inc. MiniRAE® photoionization detector (PID).
Mr. Jimmy Choy, Environmental Technician, of ATC’s New York City office, conducted the
assessment.
ATC’s findings and conclusions are based on a visual inspection, real-time environmental
measurements and conditions present in the school at the time of the assessment.