Real-time air monitoring report, PS 234M, Dec 2001

Machine-extracted title · confidence 95%

Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.

NYC-WTC_000177887–000177891
Page image
Scanned page image, NYC-WTC_000177887
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

104 East 25th Street New York, New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.

January 11, 2002

Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008

Re: Real-Time Air Monitoring P. S. 234M ATC Project No. 15-19125-0297

Dear Mr. Orlan:

ATC Associates Inc. (ATC) is pleased to provide this report of the results of real-time air monitoring conducted on December 8, 9, 11 & 12, 2001, at the referenced school. The New York City Board of Education (BOE) requested this monitoring at the recommendation of Environ Corp., the consultant to the parents association.

SCOPE OF WORK

ATC assessed the basic indoor air quality (lAQ) parameters of temperature, relative humidity, carbon dioxide (COj) and carbon monoxide (CO).

In addition, total volatile organic compounds (TVOCs), respirable particulates (PM2.5), sulfur dioxide (SO2), hydrogen sulfide (H2S), nitric oxide (NO) and nitrogen dioxide (NO2) were also measured.

Tenzin Namgyal and Wagdi Abdelshahid, Industrial Hygienists, and Marianna Medinets, Environmental Technician, from ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.

ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.

ATC recorded concentrations of respirable particulates (PM 2.5) with a Dust Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.

ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID). Nitrogen oxides and SO2 were measured using a RAE Systems, Inc. VRAE® multi-gas detector. H2S was measured using a BioSystems PhD Ultra® gas detector.

CONFIDENTIAL, CITY_21MC100_0 03444795 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000177887

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000177887Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, PS 234M, Jan 2002

NYC-WTC_000177847

Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.

Similar indexed content

Compare copies and versions →