NYC Law Department release
Independent mirror · updated as the City releases more · v1.3.2
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 2 pages

Asbestos fiber analysis results, 114 Liberty Street, April 2003

Machine-extracted title · confidence 95%

Laboratory report summarizing PCM analysis of asbestos fibers collected at 114 Liberty Street in March and April 2003.

NYC-WTC_000177528–000177529
Page image
Scanned page image, NYC-WTC_000177528
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

JLC ENVIRONMENTAL CONSULTANTS, INC. 200 Park Avenue South. Suite 1001, New York, New York 10003 Phone; (212) 420-8119 Fax; (212) 420-6092 Project No.: 03-2744 New York City D.E.P. ELAP Lab Code: 11029 Analyte: FIBERS 59-17 Junction Blvd. NIOSH and AIHA Lab Code: 100273 Date Received; 4/3/2003 Flushing, NY 11373 NVLAP Lab Code: 101953 Date Analyzed: 4/3/2003

SUMMARY OF ANALYTICAL RESULTS - PCM *' Site: ! 114 Liberty Street, New York, NY

SAMPLE # COLLECTED DESCRIPTION I LOCATION TIME(niin) VOLUME(L) FIB/FIELD RESULTS(f/cc) LAB#

001 During/ Outside Work Area/ Cedar Street/ 600 604.8 1/100 0.0008<LOD 02-April Sidewalk at Dock Entrance A 10110

002 During/ Outside Work Area/ Clean Room of 600 604,8 2/100 0.0016<LOD 02-April Personnel Decon A 10111

003 During/ Outside Work Area/ Inside Restaurant 600 604.8 2/100 0.0016<LOD 02-April Near Dock Entrance A 10112

004 During/ Outside Work Area/ Inside Stairwell to 600 604.8 3/100 0.0024<LOD 02-April Basement A 10113

005 During/ Outside Work Area/ Liberty Street Side/ 600 604.8 2/100 0.0016<LOD 02-April Walk at 114 Entrance A 10114

006 FIELD BLANK 0/100 02-April A 10115

Sample Analysis by: <LOD = Less than limit of detection which is 5.5 Fibers/100 Fields Positive Phase Contrast Microscopy (PCM) VOID1 = H.C.P. ( High Concentration of Particles) VOID2 = Overloaded Method of Sample Preparation and Analysis All samples analyzed in accordance with the NIOSH 7400 Method using "A" Counting Rules. Issue 2, August 1994

Instrumentation: (ktl^Machhiwala' ‘ Olympus PCM Model BH-2 with Walton-Beckett Graticule (100um field diameter). Laboratory Director

Report Date; April 9, 2003 JLC is responsible for only the fiber counts within the limitations of the method described as NIOSH 7400. Among other limitations, this method gives only an index of airborne fibers and provides only an estimate of asbestos concentration. Any and all claims arising out of JLC's analysis of these samples are limited in recovery to the cost of analyzing samples. JLC accepts no other liability and the client agrees to seek no costs beyond the above. Page 53 of 54

CONFIDENTIAL, SUBJECTTO PROTECTIVE ORDER NO. 1, JAN. 2013 CITY_DEP_WORBY_CANNATA_SUBP_000008869

NYC-WTC_000177528

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000177528Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →