NYC 9/11 Public Portal Document
EMSL Analytical, Jnc.
307 West 38th Street, New York, NY 10018
EMSI-
Phone; (212! 290-0061 Fax: (212! 290-0058 Email; manhattanlabeemsi.com
1
Attn: TRC Environmental Consultants Customer ID: TRCE51
1430 Broadway Customer PO:
10th Floor
New York, NY 10018 Received: 07/17/03 3:08 PM
Fax: (212) 221-7840 Phone: (212)221-7822
EMSL Order: 030313033
Project: 35052-0000-00020 I New York City Law Department 1100 EMSL Project ID:
Church St. 4th Floor Server Room
Analysis Date: 7/18/03
Asbestos Fiber Analysis by Transmission Electron Microscopy (TEM) Performed by
ERA 40 CFR Part 763 Final Rule (AHERA)
Area Analytical Asbestos
# Structures
yolume Analyzed Non Asbestos Sensitivity Concentration
Sample (Liters) (mm^) Asb Type(s) >0.5p<5 >5p (S/cc) (S/mm’) (S/cc) Notes
NA071703ASBAI 1350.00 0.0600 0 None Detected 0.0048 <16.67 <0.0048
R01
030313033-0001
NA071703ASBAI 1341.00 0.0600 0 None Detected 0.0048 <16.67 <0.0048
R02
030313033-0002
Analyst(s)
Jose Arriaga (2) Laboratory Manager
or other approved signatory
Disclaimers: The laboratory is not responsible for data repotted in structures/cc, which is dependent on volume collected by non-laboratory personnel. This lab is only responsible for
data reported in structures/mmL This report may not be reproduced, except in full, without written approval by EMSL. Thisreport must not be used to claim product endorsement. As
per40 CFR 763. the initial screening test may not be applied to samples with collected volumes of <1200 liters.
Acer diledlor NVLAP PLWl/TEM #101048-9, NY State ELAP #11506
'EM kHERA-1 1
THIS IS THE LAST PAGE OF THE REPORT.
CITY_21 MCI 00_014585140
NYC-WTC_000177287
OCR can misread numbers and units. Confirm readings against the page image before using them.