Indoor air quality field report, PS 89M, Jan 17 2002

Machine-extracted title · confidence 95%

Field report documenting indoor air quality measurements including temperature, humidity, and TVOCs at PS 89M on January 17, 2002.

NYC-WTC_000174709–000174713
Page image
Scanned page image, NYC-WTC_000174710
OCR text

OCR status: ocr · source: ours

NYC 9/11 Public Portal Document CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21MC100_014659988 TIME 8:25 LOCATION Location 501 502 Hall by 504 Staim #3 506 509(HA11) WiNDOw #IOPEN HAl by stain#* 528 519 89M Oceup. - 3 3 3 ATC ASSOCIATES, INC. INDOOR AIR QUALITY FIELD REPORT DATE_ 1/17/02 _ PROJECT NO. Temperature (F) Relative Humidity (%) Carbon Dioxide (ppm) Carbon Monoxide (ppm) 74.2 21.9 465 75.2 20.9 449 74.8 20.8 455 78.0 23.3 76.3 629 499 74.7 19.4 19.0 465 71.7 19.1 433 72.5 20.2 499 71.7 20.0 533 532 Guideline levels :ASHRAE/AIHA/ЕРА 77.0 68-75°T/winter 73-79"F/summer Zo.o 30-60% 464 Outdoor level + 700 ppm 9 ppm Comments: The assessed location(s) () Docs () Does not meet established indoor air quality guidelines. Signature: gui Chas Date: 1/17/02 NYC-WTC_000174710 Page L of 5 19125-297 Respirable Particulates(ug/m') 19 26 29 28 34 36 28 26 26 65 ug/m" 24-hour average TVOCS (Ppm) 1 ppm

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000174710Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000177950

Field report containing temperature, humidity, and gas readings from indoor air quality testing at P.S. 150M.

Similar indexed content

Compare copies and versions →