flexibility in electronic/communications distribution. The telecommunications and data
communications systems use fiber optics with high redundancy and flexibility at local
switching levels. Backup for the electrical systems is provided by six separate power feeds,
a UPS system, and 12 MW auxiliary power available from on-site emergency generators.
Water storage tanks with a 200,000 gallon capacity are available to supply the cooling
towers in the event of water failure. Chiller capacity is 4,000 tons. Rejected heat from the
computers and support machinery heat the almost 600,000 SF of administrative office
spaces. Preaction sprinklers and a dry-halon 1301 full-flooding system provide fire pro
tection.
Forest City Tech Place Associates for Full Engineering Services 05/06/92 [P2371 III-13
NYC-WTC_000166596