2.1' Central Ventilation System Visual Inspection Form Page 1 of 2
Ventilation System Identification:
Location: Area Served:
Associated mechanical room: clean Y N dry Y
stored chemicals/refuse
N Y N
Surface Component
System Components Dust/ WTC • not present
[NOTE: if component not present (NP), not found (NF) or inaccessible (I) please Debris Dust • not found
indicate in last column] Present? Present? • inaccessible
Outside air intake: Location:
Accessible for inspection? Y N (explain):
- louvers, grates and/or screens
- outside air duct
- outside air damper(s)
Air handling unit:___________________________________________________________
- outside air mixing chamber
- filter rack(s)
- filter media
- blower assembly inch blower wheel, blower housing, air vanes, in-line noise attenuators
- blower housing acoustical lining
- pre-heat coils
- heating coils
- cooling coils
- re-heat coils
- condensate drain pan
- supply air plenum
- supply air plenum damper(s)
- vibration collars
Supply air distribution:
- Supply air ducts Est. total In ft No. locations inspected
Specify type (circle): metal fibrous glass lined metal masonry fibrous glass board
flex-duct wood
- Accessible in-line fire dampers Est. total qty No. locations inspected
- Accessible turning vanes Est. total qty No. locations inspected
- In-line reheat/cooling coils Est. total qty No. locations inspected
- Supply air diffusers Est. total qty No. locations inspected
Return air distribution:
- Return air ducts Est. total In ft No. locations inspected
Specify type (circle): metal fibrous glass lined metal masonry fibrous glass board
flex-duct wood
- Return air plenum Est. total RA plenum areas No. locations inspected
- Return air plenum damper Est. total qty No. locations inspected
- Accessible in-line fire dampers Est. total qty No. locations inspected
- Accessible turning vanes Est. total qty No. locations inspected
- Return air grilles Est. total qty No. locations inspected
NYC-WTC_000160406
OCR can misread numbers and units. Confirm readings against the page image before using them.
NYC-WTC_000160406Source: NYC Law Department, mirrored locally
Instructional guidance for completing ventilation system evaluation forms, including documentation of prior inspections, maintenance records, and WTC dust assessment.
Instructional guidance for completing ventilation system evaluation forms, including documentation of prior inspections, maintenance records, and WTC dust assessment.