December 17, 2002 114 LIBERTY STREET REMOVAL OF DUST, DEBRIS, AND CONTAMINATED MATERIALS

05 AIR AND WIPE SAMPLING

PART 1 - GENERAL

1.01 RELATED DOCUMENTS:

A. Air and Wipe Sampling for Work Area clearance is also described in Section 14 Work Area Clearance.

1.02 DESCRIPTION OF THE WORK:

A. This section describes work being performed by the Owner. This work is not in the Contract Sum.

B. This section describes air and wipe sampling carried out by the Owner to verify that the building premises beyond the work area and the outside environment remains uncontaminated.

C. All sampling described in this section shall be performed by qualified industrial hygienists, who shall also be trained and certified as Asbestos Air Sampling Technicians, and shall be conducted under the guidance and supervision of a Certified Industrial Hygienist (CIH).

D. Any air monitoring that is required by OSHA is the responsibility of the Contractor and is not covered in this section.

1.03 AIR MONITORING DURING WORK:

A. The purpose of the Owner's air monitoring is to detect faults in the work area isolation such as:

1. Contamination of the premises outside of the work area with contaminated dust and debris.

2. Failure of filtration systems or rupture in the differential pressure system.

B. Should any of the above occur, immediately cease abatement activities until the fault is corrected. Do not recommence work until authorized in writing by Ambient Group, Inc.

1.04 STOP ACTION LEVELS:

A. When visible emissions occur outside the work area, or any air sample has indicated a determinant level of fiber concentrations equal to or greater than 0.01 f/cc by Phase Contrast Microscopy (PCM) via the NIOSH 7400 method, work shall stop for inspection. Ambient Group, Inc. shall inspect and determine the source of the high reading and notify the Contractor immediately.

B. If the high reading was the result of a failure of Work Area isolation measures, initiate the following procedures:

1. Clean the affected area in accordance with Section 13 Project Decontamination.

22 © AMBIENT GROUP. INC. - 2002 AIR AND WIPE SAMPLING

NYC-WTC_000155487

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000155487Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →