ADDENDUM #2
World Trade Center Dust Cleaning Program
Monitoring Contract Scope of Work
whether or not there are materials that are likely not associated with WTC-
related dust such as building-related asbestos-containing materials, animal
. carcasses, delaminating lining material, visible mold growth, water damage,
fecal matter, feathers or other evidence of animals, etc.
Historical Assessment
The evaluation team shall attempt to describe any other available information from site
occupants or building managers, such as the known status of system operating conditions at the
time of the WTC collapse, ventilation system maintenance (i.e., cleanings, filter changes, or
replacement since the WTC collapse).
(
Based on these assessments, to the best of his/her ability the Environmental Professional
will state a general impression of the overall cleanliness of each component, and whether or
not it appears to be impacted by WTC-related dust
6.5.2.3 Environmental Sampling Procedure
If the evaluation team determines that the ventilation equipment appears to have been impacted
by WTC-related dust, cleaning will be recommended and environmental sampling will not be
required. This information shall be included in the HVAC system evaluation report. The
HVAC system evaluation report must be sent to EPA electronically in PDF format.
In the absence of environmental sampling that indicates otherwise, WTC-related dust shall be
assumed to be an asbestos-containing material and cleaning procedures shall be performed in
accordance with procedures for asbestos decontamination (see section 5.0).
If dust or debris is present and it is not apparent that it is related to the collapse of the WTC, a
maximum of 5 bulk samples will be collected and analyzed for pH, fibrous glass and crystalline
silica. These samples and copies of necessary documentation shall be shipped daily by courier
for next day delivery to EMSL Analytical Inc., 107 Haddon Avenue, Westmont, NJ 08108 (Tel:
856-858-4800). This data will be used to determine if the sampled dust is fi’om the collapse of
the WTC. Dust will be considered WTC-related if: pH is 9 or above; fibrous glass content is
between 30 and 40 % and crystalline silica content is 5% or greater. Laboratory data will be
reported back to the Monitoring Contractor and shall be included in the HVAC system
evaluation report. The HVAC system evaluation report must be sent to EPA electronically in
PDF format.
Sampling Procedures
1. Sampling of interior dust may only be performed by the Environmental Professional.
2. Minimum personal protective equipment used by the Environmental Professional shall
include a disposable protective coveralls, a PlOO respirator, safety glasses, and disposable
gloves.