Accessible in-line fire dampers, accessible turning vanes, in-line reheat/cooling coils, supply
air diffusers - roughly estimate the number of each type of component present. If the
component is completely inaccessible, the estimated quantity should be listed as “unknown”. If
the component is not present, the estimated quantity is zero. Indicate the number of locations
where the listed component was accessed for inspection in the spaces provided.
Other components-use this space to describe any other component not already included on the
form that is part of the mechanical make-up air system.
Other information -
Indicate the level of visible particulate loading on the filter. Light - lightly visible accumulation.
Moderate — obvious visible accumulation. Heavy - heavy accumulation that may result in filter
panel disfiguration or filter bypass.
Indicate whether damaged interior acoustical duct lining is observed. If possible, note the
location where the damage is observed.
Indicate obvious sources of filter bypass, e.g., improper size of filters, tracks, damaged or
missing tracks, or other causes of poor fit in tracks.
General impression - this space is for the HVAC Evaluator’s general impression of whether or
not cleaning is indicated based on the presence of WTC dust. The HVAC Evaluator should note
any other comments that are deemed relevant to the determination of WTC dust or comments on
conditions that would likely impact the scope or feasibility of cleaning.
2.4 Passive Shaft/Duct
Perform the most vigorous visual inspection possible. Minimum inspection equipment should
include screwdrivers, a utility knife (for opening panels, diffusers, grilles, etc. that are painted or
caulked in place), telescoping mirror, flashlight, and portable borescope. In addition, the HVAC
Evaluator should attempt to penetrate visible dust to determine if a WTC layer is present.
When a ventilation system component is accessed for inspection, indicate whether or not surface
dust/debris is present, and whether or not suspect WTC dust is present in the second and third
columns, respectively.
Outside air intake, exhaust outiet/iouver - please check for all components that apply. If a
listed component is not part of the system, then indicate “not present” (NP) in the right-hand
column. If the component is likely to be present, but it cannot be located, indicate “not found”
(NF) in the right-hand column. If the listed component is present and is located, but is not
accessible for inspection, indicate “inaccessible” (I) in the right-hand column.
Supply air distribution/retum air distribution - Roughly estimate the total number of supply
air outlets or return air inlets in the passive shaft/duct, and indicate the number of locations
where the outlets or inlets were accessed for inspection in the spaces provided. Also circle the