Guidance for Ventilation System Evaluation Form Page 2 of?

borescope. In addition, the HVAC Evaluator should attempt to penetrate visible dust to determine if a WTC layer is present.

When a ventilation system component is accessed for inspection, indicate whether or not surface dust/debris is present, and whether or not suspect WTC dust is present in the second and third columns, respectively.

Associated Mechanical Room - indicate if there is a mechanical room associated with the central ventilation system, e.g., the air handling unit is located in the mechanical room, the mechanical room is an air mixing chamber for the air handling unit, etc.

Outside air intake, air handling unit - please check for all components that apply. If a listed component is not part of the system, then indicate “not present” (NP) in the right-hand column. If the component is likely to be present, but it cannot be located, indicate “not found” (NF) in the right-hand column. If the listed component is present and is located, but is not accessible for inspection, indicate “inaccessible” (I) in the right-hand column.

Supply air distribution - Roughly estimate the total linear footage of supply air ducts associated with the central ventilation system, and indicate the number of locations where the interior of the duct was accessed for inspection in the spaces provided. Also circle the type of material from which the duct is constructed (e.g., metal, fibrous glass lined metal, masonry, fibrous glass board, flex duct, wood). If more than one type of duct material is present, circle all that apply.

Accessible in-line fire dampers, accessible turning vanes, in-line reheat/cooling coils, supply air diffusers - roughly estimate the number of each type of component present. If the component is completely inaccessible, the estimated quantity should be listed as “unknown”. If the component is clearly not present, the estimated quantity is zero. Indicate the number of locations where the listed component was accessed for inspection in the space provided.

Return air distribution - roughly estimate the total linear footage of return air ducts associated with the central ventilation system, and indicate the number of locations where the interior of the duct was accessed for inspection in the spaces provided. Also circle the type of material from which the duct is constructed (e.g., metal, fibrous glass lined metal, masonry, fibrous glass board, flex duct, wood). If more than one type of duct material is present, circle all that apply.

Return air plenum, return air plenum damper, accessible in-line fire dampers, accessible turning vanes, return air grilles - roughly estimate the number of each type of component present. If the component is completely inaccessible, the estimated quantity should be listed as “unknown”. If the component is clearly not present, the estimated quantity is zero. Indicate the number of locations where the listed component was accessed for inspection in the space provided.

Other components-use this space to describe any other component not already included on the form that is part of the central ventilation system.

NYC-WTC_000139875

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000139875Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →