6. HVAC systems that have been impacted by dust or debris from the collapse ofthe World Trade Center will be cleaned. In the event that a HVAC system for an entire building requires cleaning, a separate, site specific contract will be awarded by DEP for this work. If only a portion of a HVAC system requires cleaning, then the cleaning contractor will conduct the cleaning utilizing specialized labor trained and experienced in duct cleaning. a. The monitoring contractor shall schedule and oversee the cleaning of HVAC systems. b. The Monitoring Contractor shall inspect HVAC systems or portions thereofcleaned to verify cleanliness. Ifvisible dust or other contaminants are evident through visual inspection or testing, then the Monitoring Contractor will direct the HVAC cleaning contractor to relean those portions of the system where dust or other contaminants are present and reinspect. c. HVAC cleaning, and cleanliness inspections shall be conducted in accordance with the National Air Duct Cleaners Association (NADCA) General Specification for the Cleaning of Commercial Heating, Ventilating and Air Conditioning Systems and the NADCA Assessment, Cleaning and Restoration Standard (ACR 2002).

7. Sampling of residences and common spaces where cleaning has not been requested a. Based on consultation with resident, aggressive or modified aggressive air sampling will be conducted. 1. Before beginning aggressive air sampling, a 1 horsepower electric leafblower shall be used to direct exhaust air against walls, ceilings, floors and other surfaces. This shall continue for at least five minutes per 1,000 square feet of floor. When directing the exhaust, caution shall be taken to minimize disturbance and potential damage to furnishings and personal belongings ii. Residents shall not be present in their residence during aggressive air sampling activities. iii. Personal protective equipment including disposable clothing, gloves, and respirators shall be worn during aggressive air sampling activities. iv. HVAC systems shall be shut down or isolated locally during aggressive air sampling. V. Room and window air conditioners shall not be operated during aggressive air sampling. vi. Leaf blowers shall not be employed for modified aggressive air sampling. vii. All other procedures are identical for aggressive and modified aggressive air sampling, unless otherwise noted. b. At least one 20-inch fan shall be placed in the center ofeach room sampled. One fan per 10,000 cubic feet ofroom space shall be used. The fans shall be operated on slow speed and pointed toward the ceiling. The fans shall run for at least 15 minutes prior to the start of sampling. The fans shall operate continuously throughout sampling and shall not be turned off until sampling is completed. c. For studio apartments 3 air samples shall be collected. For 1 -bedroom apartments and

7

NYC-WTC_000138781

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000138781Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →