NYC 9/11 Public Portal Document
10/16/201 14:19 7187298677 THE METRO GROUP PAGE 06/14
THE METRO GROUP, INC.
Care
Servicing Water Systems with Environmental
50,23 Twenty-Third Street
Long Island City, NY 11101
TEL:(718)729-7200
FAX:(718)7298677
CERTIFICATE OF ANALYS
METAL SCAN ANALYSIS
BROWN HARRIS STEVENS ANALYSIS NO.; 8371-2
NEW YORK NY
DATE: 101151'01
SAMPLING DATE: 9126101
SOURCE OF SAMPLE - WATER FROM 21 SOUTH END AVE. LOBBY BATHROOM
w
Tests: Chemical analysis for conformance with Safe Drinking Water
PARAMETER YOUR SAFE DRINIgNG WATER AT
RESULT MAX. CONTAMINANT LEVEL
Chloride 14.1 250 mglt
Color 10.0 15 Units
Conductivity 124
umhslcm
Fluoride 0.84 2.2 mg!L
-2.88 Units
Connsivity (L.S.L) mg1L
Nitrate N 0.27 10.0
Units
r
Odor 0 3
6.9 6.5-8.5 Units
pH 250
Sulfate 7.5
Total Alkalinity 21.8 mg/L
Total Dissolve Solids 112 mg/i..
Turbidity <1.0 5.0 ntu
Arsenic <3.0 50.0 ug/-
Barium <0.20 2.0 mg/L
Cadmium <5.0 5.0 ug/L
Calcium 8.67 mglL
Chromium <0.01 1.0 MA
Copper <0.04 1.3 mg/L
Lead <1.0 15:0 ug/L
Iron 0.04 .30 mg/L
Magnesium 2.18 mg/L
Manganese 0.02 0.30 mg/L
Sodium 10.8 250. mg/L
Total Hardness
2lnc <0.02 5.0 mg/L
exceeds
CODES: MCL (Maximum Contaminant Lever), mg/L (milliigrams/llter - ppm), " indicates analyte
EPAfSDWA proposed maximum contamination level.
COMMEN'T'S: ALL PARAMETERS FALL WITHIN THE MAXIMUM CONTAMINANT LEVELS STIPULATED
FOR A SAFE DRINKING WATER,
JD:gn twckmde&
LABORATORY MANAGER
LI Responsible Cre'
__,Goad themistry arWork.
NYC-WTC 000120378