BEBE: United States Environmental Protection Agency. ‘
Bead Work Area: Portion of the Work Area that contains one type of ACM and/or where one
atateinent is used.
FE Contrast Microscopy: “PCM” shall mean the measurement protocol for the assessment for the fiber
ee of air. For PCM analysis, the clearance air monitoring shall be considered satisfactory when every
Pate is less than or equal to 0.01 f/cc or the background concentrations, whichever is greater.
Polarized Light Microscopy: “PLM"shall mean the measurement protocol for the assessment for the
BF ssbestos content of bulk materials. For PLM analysis, the New York City and EPA Regulatory limit is
ee 1.0%.
Ree
3 ‘Transmission Electron Microscopy: “TEM"shall mean the measurement protocol for the assessment for
the asbestos fiber content of air. For TEM analysis, the clearance air monitoring shall be considered
F atisfactory when the requirements stated in 40 CFR Part 763, Subpart E, Appendix A, Section IV are met.
For the purposes of our testing the regulatory limit is 70 asbestos structures per mm2.
4.0 Scope of Work
4.1 Bulk Sampling Procedures
ALC’s licensed technicians worked under the guidance provided by the EPA guidelines for
asbestos-“‘Asbestos in Buildings: Simplify Sampling Scheme for Friable Surfacing Materials.”
‘This sampling procedure uses random sampling to ensure that the samples are representative of the
sampling area. ALC’s inspectors:
1, Identified all friable surfacing materials and grouped them into homogenous sampling
areas by floor
2. Prepared diagrams of each sampling area
| 3. Determine the number of samples to collect (9 samples per homogenous areas are
| recommended) Determine sampling locations
| 4. Collect samples
| 5. Fill out chain of custody
6. Send samples to a qualified laboratory
Due to the insufficient amount of dust and debris in the apartment units and public areas of the
building, we were unable to collect the optimum number of samples suggested in the above
referenced guidelines.
With the guidance of the above referenced document and NYCDEP we went to each floor and
assessed each apartment on each floor for visible dust and debris. Upon completion of the initial
assessment and bulk sample collection, ALC determined that there were no elevated asbestos
levels present above the guidelines in any of the apartments where samples were taken.
If any dust and/or debris was found in the apartment we collected a bulk sample and sent it to the
laboratory for analysis.
¥ Ifno sample could be taken due to insufficient material present at the time we were in the
a ‘apartment, the inspector documented this on the log.
NYC-WTC_000117671