C. Airborne Metals — Ten (10) indoor samples were collected in total. The sample
locations included the 33 1, 29th, 20th, 19th, 17th, 12th, 10th, 7th, 5th and 1' floor. An
outside air sample was also collected on the 7th floor. All indoor sample locations
were in occupied areas near supply air diffusers. Samples were collected for eight
hours at 2 liters/minute. They were analyzed for cadmium, chromium, copper, iron,
lead, manganese, nickel, silica and zinc by method NIOSH 7300. All results were
below OSHA PEL and American Conference of Governmental Industrial Hygienist
(ACGIH) Threshold Limit Values (TLVs). Please refer to Table 1, insert and
Appendix A for results and regulatory standards. Please refer to the floor plans in
Appendix C and photographs in Appendix D for specific sample set-up and
locations.
D. Airborne Mercury - Ten (10) indoor samples were collected in total. The sample
locations included the 33111, 29th, 20th, 19th, 17th, 12th, 10', 7th, 5th and floor. An
l
a
outside air sample was also collected on the 7th floor. All indoor sample locations
were in occupied areas near supply air diffusers. Samples were collected for eight
hours at 0.2 liters/minute and analyzed by method NIOSH 6009. All results were
below the OSHA PEL and below the ACGIH TLV. Please refer to Table 1, insert
and Appendix A and B for results and regulatory standards. Please refer to the floor
plans in Appendix C and photographs in Appendix D for specific sample set-up and
locations.
II. HVAC System/Visual Inspection
The HVAC system inspection consisted of a visual inspection of the mechanical rooms and
associated fan units on the 33111, 29th, 20th, 19th, 17th, 12th, 10th, 7th, and 5th floors. Please note that
an inspection of the interior of associated ductwork was not performed. Also, no data regarding
balancing and air velocities were obtained or analyzed. In general, the mechanical equipment
rooms (MERs) were clean and well lit. Some of the MERs had stored materials present. There
were no dust accumulations in the air mixing chambers of the HVAC units and the filters were in
good condition. The coils and condensate drip pans (CDPs) of the HVAC units were clean and
there was no standing water present on the day of the survey. The CDP of the west side HVAC
unit on the 12th floor, however, needs to be repaired. Please refer to Appendix C for floor plans
indicating HVAC unit locations. Please refer to Appendix E for inspection results, and Appendix
F for photographs of the individual HVAC units.
Project: 220490
Page 2
NYC-WTC 000105540