PCM AIR SAMPLE RESULTS
Client: Bovis LendL ase Date Collected: 02/15/02
• Date Rec'd (lab): 02/16/02
Project #: MBO-025AB Analysis Date: 02/16/02
Analyst: L. Chivarini
Sample Location: The Millenium Hilton
55 Chruch Street Analytical Method: NIOSH 7400
New York, New York
• Field Technician: K. Laverenko/S. Manukov
Sample #: Sample Location:
Sample I . Work 02PCM # Volume I Duration Concentration
Type Location (min.) f/cc
Leonard Lewis _ Personal —Entire
02Pers _ 2874 75 30 0.0360
STEL Building
Leonard Lewis Personal Entire
04Pers -- - -------_.pll 2876 325 130 0.0083
Building
._._..Leanard_Lewis._._._.. Personal Entire
07Pers 2879 312 130 0.0086
PII TWA Building
._._.L.eanard.LP_w. ._._.. Personal Entire
10Pers 2882 400 160 0.0067
Building
12 Blank Blank N/A 2884 0 0 N/A
13 Blank Blank N/A 2885 0 0 N/A
Total Duration Sampled (min.) 450
Short Term Exposure Limit (STEL) 0.0361
8 hr. Time Weighted Average (TWA) 0.009,
(c) Permissible exposure limits (PELS)
(c)(2) Excursion limit The employer shall ensure that no employee is exposed to an airborne concentration of asbestos in excess of 1.0 fiber per cubic
centimeter of air (1 f/cc) as averaged over a sampling period of thirty (30) minutes, as determined by the method prescribed in Appendix A to this section, or
by an equivalent method.
(c)(2) Excursion limit. The employer shall ensure that no employee is exposed to an airborne concentration of asbestos in excess of 1.0 fiber per cubic
centimeter of air (1 f/cc) as averaged over a sampling period of thirty (30) minutes, as determined by the method prescribed In Appendix A to this section, cr
by an equivalent method.
RespIratory Protection: Half face negative air respirator equip with HEPA cartridge.
Respiratory
* Limit of quantitation based on volume of air collected and 5.5 f/100 fields.as per the NIOSH 7400 method. The report value is
calculated by using the higher value of either the actual concentration or the limit of quantification reported at P(0.05) indicating the 95%
confidence level at 2 standard deviations. " Sample information is provided by the client & presented as stated. "' Laboratory QC
data available upon request "" The laboratory has no control over air sampling collection. Reports are the confidential property of our
clients. This certificate of analysis/report shall not be used by the client to claim product endorsement by the National Voluntary
Laboratory Approval Program (NVLAP) or any agency of the United States Government This certificate of analysis/report shall not be
reproduced except in full, without the written approval of Testwell Laboratories, Inc.
Deborah McCarl - Laboratory Director