NYC 9/11 Public Portal Document
10/16/2002 15:21 FAX 212 353 8306 ATC 13015
Attn: Benjamin Sallena Received: 10/9/02 100:00 PM
ATC Associatcs Inc. ATC Group #: 8950
104 East 25th Street Analysis Date: 10/14102
New Yozk NY 10010
Fax: (212)353-3599 Phone: (212)353.8260
Project: DEP Clean-up ATC Project #: 22905-0002
125 Cedar Street, New York, NY
EPA PCMe Method Via Transmission Electron Microscopy
Nor Asbestos EPA FCMe
Asbestos PCM .4sbestos Asbenos % of (TEM)
Sample Volume Fiber F/cc Type(s) Fibers moral F/cc Notes
A 4N 20 3600.00 4 0.001 None [retsaed 0 0 <0.0002 Cellulose • 2 Sructures. Gypsum - 2 Structures
8950 -I3
A 4T+i 31 3600.00 10 0.001. None Detected 0 0 <0.0002 Cellulose -5 Structures, Gypsum -5 Suuctures
5450 -19
A 4N 22 3600.00 16 0.001 (done Detected 0 0 <0.0002 Cellulose • 3 Structures. Gypsum -13
8950 -20 Structures
4$1 23 3600,00 1 0.001 None Detected 0 0 <0.0002 Cellulose • 1 Structure -
8950 -21
A 4N 244 3600.00 17 0.002 .None Detected 0 0 <0 0002 Cellulose • 4 Structures, Gypsum -13
3930 -22 Structures
A 4 25 3600.00 l4 0.001 None 0elected 0 0 < 0.0002 Cellulose - 8 Structures, Gypsum - 5 Structures
8950 -23
A4 26 3600.00 8 0.001 -. — None '3eteeted 0 0 <0.0002 Cellulose -6 Structures, Gypsum- 2 Structures
89.50 -24
A 3S27 3600.00 - 10 0.001 None Detected 0 0 <0.0002 Cellutras -5 Structures. Gypsum • 4
8950 -25 Structures, Glass'- I Structure
A 3S 28 3(,00.00 8 0.001 None Detected 0 0 <0.0002 Cellulose - 6 Structuures, Gypsum -2 Structures
8950 -26
A 3S 29 3600,00 88 U.UU1 None etectec U U tU.UUUh Celluross-4 Structures. Gypsum .4 Slnxxures
9950 -27
OV - MICHAEL A. GORYCKI, M.D.
ROMANPEYS I
Analyzed by: Approved by: —
ATC is not responsible for dam reported in fibers o, which Is dependent on volume collected by non-18bar'atery personnel. The move report relates only to the items tested. This
report may not be reproduced, except in Fuit. without wcten approval by ATC Assopalef Inc.
Analysi$ peAarmed try ATC Assodates Inc tNY ELAP #10879).
Fcrtl Grtd Openings from each of the samples Hare eserrined for structures greaser than Lin length and heving a length-to-width ratio greater than 31
Wednesday, Ocrober I6, 2002 Page 3 of 6