NYC 9/11 Public Portal Document
JLC ENVIRONMENTAL CONSULTANTS, INC.
200 Park Avenue South, Suite 1001, New York, New York 10003
Phone: (212) 420-8119 Fax: (212) 420-6092
Project No.: 01-2089003
Rose Associates Inc. ELAP Lab Code: 11029 Analyte: FIBERS
200 Madison Ave. 5th Floor NIOSH and AIHA Lab Code: 100273 Date Received: 10/19/2001
New York, NY 10016 NVLAP Lab Code: 101953 Date Analyzed: 10/19/2001
Batch #: 011OA792
SUMMARY OF ANALYTICAL RESULTS
Site: L 21 West Street, New York, NY
SAMPLE #
COLLECTED DESCRIPTION / LOCATION TIME(min) VOLUME(I) FIB/FIELD RESULTS(f/cc)
LAB#
013 Ambient/ 11th Floor/ Apt. I1E/ At the North 120 1846 2/100 <0.001<LOD
Section of e Living Room
A 8054
014 Ambient/ 11th Floor/ Hallway Between Apt. 11H 120 1846 2/100 <0.001<LOD
18-October and Apt. 11J
A 8055
015 Ambient/ 9th Floor! Apt. 9C At the North Section o 120 1846 2/100 <0.001<LOD
18-October the Living Room
A 8056
016 Ambient/ 9th Floor/ Hallway Between Apt. 9H and 120 1846 6/100 0.002
18-October 9J
A 8057
017 Ambient/ 8th Floor/ Apt. 8E/ At the North Section 120 1846 5/100 0.001<LOD
18-October of the Living Room
A 8058
018 Ambient/ 8th Floor/ Hallway Between Apt. 8H and 120 1846 7/100 0.002
18-October 8J
A 8059
Sample Analysis
s by: <LOD = Less than limit of detection which Is 5.5 Fibers/ 100 Fields
Positive Phase Contrast Microscopy (PCM) VOIDI = H.C.P. (High Concentration of Particles)
VOID2 = Overloaded
Method of Sample Preparation and Analysis:
All samples analyzed In accordance with the NIOSH 7400 Method using "A" Counting Rules. Issue 2, August 1994
Instrumentation:
Olympus PCM Model BH-2 with Walton-Beckett Graticule (100um field diameter). GU am ac Iwa a
Laboratory Director
Report Hate: October 23, 2001
JLC Is responsible for only the fiber counts within the limitations of the method described as NIOSH 7400. Among other limitations, this
method gives only an index of airborne fibers and provides only an estimate of asbestos concentration. Any and all claims arising out of
JLCs analysis of these samples are limited in recovery to the cost of analyzing samples. JLC accepts no other liability and the client agrees
to seek no costs beyond the above.
Page 3 of 5
NYC-WTC 000094644
OCR can misread numbers and units. Confirm readings against the page image before using them.