NYC Law Department release Independent mirror · updated as the City releases more · v1.5.1 ☕ Buy me a coffee
← Document results/DEP Box 66/NEWE 1/11/2002 AD 31456 - AE00110 Batches 16390 16391 16402 copies made
Document / 60 pages
Method 200.8 ICP-MS lab results, NEWE samples, Jan 11, 2002
Machine-extracted title · confidence 85%
ICP-MS analysis of water samples using Method 200.8 with elemental measurements (Be, Sc, Mn, In, Sb, Ho) and quality control replicates performed on January 11, 2002.
Concentration Results
Analyte Mass Meas. Intens. Mean Meas. Intens. RSD Net Intens. Mean Cone. Mean Cone. RSD Sample Unit
r Be 9 24107.165 1.115 0.041 51.76273 1.03 ug/L
|> Sc-1 45 588717.080 1.918 588717.080 ug/L
L Mn 55 849376.603 2.593 1.442 49.99860 3.48 ug/L
r> In 115 1244025.503 0.486 1244025.503 ug/L
I Sb 121 404708.221 0.239 0.325 50.48208 0.72 ug/L
L Sb 123 312858.482 1.132 0.251 50.85195 0.66 ug/L
r> Ho 165 1692831.455 2.277 1692831.455 ug/L
L Tl 205 1303607.485 3.105 0.770 49.77272 2.27 ug/L
QC Calculated Values
Analyte Mass QC Std % Recovery Int Std % Recovery Spike % Recovery Dilution % Diff Dup. Rei. % Diff
r Be 9
|> Sc-1 45 92.720
L Mn 55
r> In 115 94.332
I Sb 121
L Sb 123
r> Ho 165 94.254
L Tl 205
Calibration
Analyte MassCurve Type Correlation Coefficient
r Be 9Linear Thru Zero 0.999992
|> Sc-1 45Linear Thru Zero
L Mn 55Linear Thru Zero 0.999983
r> In 115Unear Thru Zero
1 Sb 121 Linear Thru Zero 0.999998
L Sb 123Linear Thru Zero 1.000000
r> Ho 165Linear Thru Zero
L Tl 205Linear Thru Zero 0.999977