REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample HILLVIEW
Distribution Laboratory
I
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 58
Dr. Ian Hurley ID of Source:
Received LK Collection 10/19/2001 AT 9:30:00
Bottle C0325,Q9370,9359,9357,P9398, Submitted 10/19/2001 AT
Collected By: TIGLAO/ODOMIRO Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival? : YES
Report
Sample No. AD25733
Method Test Description Results Units MDL Analyzed on Validator
Hexachlorocyclopentadiene <MDL ug/L 0.10 10/31/2001 DLV
Metolachlor < MDL ug/L 0.75 10/31/2001 DLV
Metribuzin <MDL ug/L 0.15 10/31/2001 DLV
Molinate < MDL ug/L 0.90 10/31/2001 DLV
Simazine <MDL ug/L 0.40 10/31/2001 DLV
Terbacil <MDL ug/L 2.0 10/31/2001 DLV
Recoveries for 3 of the 18 compounds in the MDL and LCS Standards were outside of their acceptance ranges.
Recoveries for 4 of the 18 compounds in the Spiked Sample were outside of their acceptance ranges. The result for
bis(2-Ethylhexyl)phthalate of 3.4 ug/L could be due to collection or laboratory contamination. This value is below
the NYSDOH MCL.
GCMS Scan For Unknowns
Other unknown compounds ug/L 11/29/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35-550 amu using a mass spectrometer, does not reveal
the presence of non-target compounds.
Approved Pam Dilsizlan QA Officer Date Approved: 12/20/2001
Environmental Laboratories emailed Original 12/20/2001
NYS ELAP # 10108 Page 7 of 7