NYC 9/11 Public Portal Document
REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample HILLVIEW
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 3
Dr. Ian Hurley ID of Source:
Received KM Collection 10/10/2001 AT
Bottle c9879,k7403,2577,7242,p9914,9 Submitted 10/10/2001 AT
Collected By: TIGLAO/PAKHLA Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival? : YES
Report
Sample No. AD24694
Method Test Description Results Units MDL Analyzed on Validator
Butachlor <MDL ug/L 0.40 10/22/2001 DLV
EPTC < MDL ug/L 1.0 10/22/2001 DLV
Hexachlorobenzene < MDL ug/L 0.10 10/22/2001 DLV
Hexachlorocyclopentadiene < MDL ug/L 0.10 10/22/2001 DLV
Metolachlor < MDL ug/L 0.75 10/22/2001 DLV
Metribuzin < MDL ug/L 0.15 10/22/2001 DLV
Molinate < MDL ug/L 0.90 10/22/2001 DLV
Simazine < MDL ug/L 0.40 10/22/2001 DLV
Terbacil < MDL ug/L 2.0 10/22/2001 DLV
The level for bis(2-Ethylhexyl)phthalate in the Laboratory Blank was 1.3 ug/L. Recoveries for 5 of the 18
compounds in the MDL Standard were outside of their acceptance ranges. Recoveries for 2 of the 18 compounds in
the LCS Standard were below their acceptance ranges. Recoveries for 5 of the 18 compounds in the Spiked
Sample and the Spiked Duplicate Sample was outside of their acceptance ranges.
GCMS Scan For Unknowns
Other unknown compounds ug/L 11/13/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35-550 amu using a mass spectrometer, does not reveal
the presence of non-target compounds.
Approved Pam Dilsizian QA Officer Date Approved: 12/24/2001
Environmental Laboratories emailed Original 12/24/2001
NYS ELAP # 10108 Page 7 of 7
NYC-WTC_000027655
OCR can misread numbers and units. Confirm readings against the page image before using them.