NYC 9/11 Public Portal Document
REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
@goncy:New York City DEP DWQC Sample MANHATTAN
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 32350 DEP LAB #29206
Dr. Ian Hurley ID of Source:
Received KM Collection 9/26/2001 AT 12:16:00
Bottle c66,k7950,7651,7423,8794,8788, Submitted 9/27/2001 AT 11:16:00
Collected By: GERTSIK Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival?: YES
Report
Sample No. AD23721
Method Test Description Results Units MDL Analyzed on Validator
bis(2-Ethylhexyl)phthalate 210 ug/L 0.60 10/9/2001 DLV
Butachlor < MDL ug/L 0.40 10/9/2001 DLV
EPTC < MDL ug/L 1.0 10/9/2001 DLV
Hexachlorobenzene < MDL ug/L 0.10 10/9/2001 DLV
Hexachlorocyclopentadiene <MDL ug/L 0.10 10/9/2001 DLV
Metolachlor <MDL ug/L 0.75 10/9/2001 DLV
Metribuzin <MDL ug/L 0.15 10/9/2001 DLV
Molinate <MDL ug/L 0.90 10/9/2001 DLV
Simazine < MDL ug/L 0.40 10/9/2001 DLV
Terbacil <MDL ug/L 2.0 10/9/2001 DLV
Recoveries for three of the eighteen compounds in the MDL Standard and the LCS Standard were outside of their
acceptance ranges. Recoveries for two of the eighteen compounds in the Spiked Sample and the Spiked Duplicate
Sample were outside of their acceptance ranges. The level for bis(2-Ethylhexyl)phthalate in the Laboratory Blank
was 0.76 ug/L. The result of 210 ug/L for this sample may be due to a laboratory accident.
GCMS Scan For Unknowns
Other unknown compounds ug/L 10/17/2001 DLV
A scan of the extract prepared for the 508 analysis, from 35-550 amu using a mass spectrometer, does not reveal
the presence of non-target compounds.
Stat charge for VOLATILE organic Completed 9/27/2001 12:06 AM SV
Approved Pam Dilsizian QA Officer Date Approved: 11/5/2001
Environmental Laboratories emailed Original 11/5/2001
NYS ELAP # 10108 Page 7 of 7
NYC-WTC_000026821
OCR can misread numbers and units. Confirm readings against the page image before using them.